PFP (Passive Fire Protection)
Cafco Fendolite MII System
Cafco Fendolite MII System Arrangement
To protect Structural steel, Equipment & vessels, Spheres from Hydrocarbon fire attack with the application
Surface Preparation - Pin install
Surfaces to be coated must be free from oil, grease and visible moisture (including condensation), dirt, loose paint, dust, loose mill scale or other materials or conditions likely to impair adhesion of the CAFCO¢ç PSK 101
Application & Inspection of PSK 101
100-150 microns wet film thickness (WFT) / 55-82 microns dry film thickness (DFT)
PCG Mesh Application
Mixing
Add 15 to 19 liter water for 20 kg bag of Cafco Fendolite MII Mixing the materials minimum 3 minutes
slump Test, Density Test
Mason Work, Spec thickness check
Trowel the coated surface even and check the actual thickness
Curing
Curing time depend on the site temperature and spec thickness
Client Inspection
Curing time depend on the site temperature and spec thickness
Promaseal Silicone Sealant - Application, Mastic Inspection